ToggleAn LED exit light may have a rated LED life of 50,000 hours, but that does not mean the complete fitting will remain serviceable for the same period. The LED, rechargeable battery, charger and control electronics all age differently.
For electricians, facility managers and fire protection contractors, the more useful question is whether the exit light still performs correctly when mains power fails.
How long does the LED in an exit light last?
Modern LED exit lights can have long rated lamp lives. Fire Factory’s EX80LED blade exit light, for example, lists an LED lifetime of 50,000 hours.
That figure applies to the LED light source. It should not be interpreted as a guarantee that the battery, charger and complete fitting will operate for 50,000 hours without maintenance.
The working condition of an exit sign also depends on emergency operation, battery capacity, electrical components, sign visibility and physical condition. When choosing LED exit lights, it is worth checking the complete specification rather than comparing products on LED lifespan alone.
Why the battery may need attention first
The rechargeable battery keeps the exit light operating when the normal power supply is lost.
Battery condition changes over time and can be affected by factors such as battery chemistry, temperature, charging conditions and discharge cycles. For that reason, assigning one fixed replacement age to every emergency lighting battery can be misleading.
A battery can also deteriorate while the exit sign appears to work normally on mains power. The problem may only become obvious when the fitting has to operate in emergency mode for an extended period.
Fire Factory supplies replacement batteries for emergency exit lights in different battery types, voltages and capacities. The replacement must suit the specific fitting. Physical size alone is not enough to determine compatibility.
Testing tells you more than age
Australian emergency lighting requirements focus on how a fitting performs when normal power is unavailable.
Under the NCC framework, required emergency lighting must be capable of operating at the prescribed level for at least 90 minutes. Fire Factory’s existing compliance guidance also identifies a six-monthly 90-minute discharge test as part of routine emergency and exit light servicing.
Some products are designed for longer emergency operation. The EX80LED, for example, specifies an emergency duration of at least two hours. Other models may have different ratings.
The important point is simple: an exit light that appears normal during everyday operation still needs to demonstrate that its emergency supply can support the required operating period.
When should an LED exit light be replaced?
Age is only one factor. Replacement becomes more important when faults affect reliable operation or visibility.
Common warning signs include failure during a discharge test, inconsistent emergency operation, charging problems, damaged housings or diffusers, poor sign visibility and recurring electrical faults.
Replacement may also be more practical when suitable spare parts are no longer available or a fitting repeatedly requires attention.
Physical condition matters as well. A functioning LED does not make an exit sign satisfactory if the diffuser is badly damaged, the pictogram is difficult to see or the fitting is unsuitable for the conditions in which it is installed.
Battery replacement or complete fitting replacement?
A failed battery does not necessarily mean the complete exit light needs to be replaced.
If the fitting is otherwise in good condition, the charging system is operating correctly and a compatible battery is available, battery replacement may be sufficient. The fitting should then be tested to confirm that it performs correctly in emergency mode.
Complete replacement becomes more appropriate when problems extend beyond the battery. Persistent charging faults, damaged components, unreliable electronics or repeated failures can make replacing the entire fitting more practical than continuing to repair it.
Maintenance records can help with that decision. A history of discharge-test failures and repeated repairs often provides more useful information than the age of the fitting alone.
FAQs
How many years does a 50,000-hour LED exit light last?
A 50,000-hour rating refers to the LED light source, not the guaranteed life of the complete exit fitting. Batteries, chargers and other electrical components may require maintenance or replacement much earlier.
How often should exit light batteries be replaced?
There is no single replacement interval that applies to every battery. Battery chemistry, operating conditions and discharge history all affect service life. Regular testing is the better way to identify batteries that can no longer provide the required emergency operation.
Should I replace the battery or buy a new exit light?
If the fitting is sound and only the battery has deteriorated, a compatible replacement battery may be sufficient. If the fitting has charging faults, damaged components, repeated failures or unavailable spare parts, replacing the complete unit may be the better option.
Choosing the right replacement
Contractors looking for LED exit lights in Sydney can choose from Fire Factory Australia’s range of blade, quickfit, recessed, waterproof, surface-mounted and jumbo exit lights.
For businesses looking for an emergency lighting supplier in Sydney, Fire Factory has locations in Smithfield and Granville and supplies trade customers across Australia.
Do not judge an exit light by its LED rating alone. The light source may be rated for 50,000 hours while the battery or other components require attention much sooner.
When replacement is due, Fire Factory Australia supplies LED exit lights, emergency lighting products and compatible replacement batteries for commercial and trade applications. Check the fitting specification carefully, or contact our team if you need help identifying the right replacement.