Description
Fire Detection, Control Panels and System Accessories
Extender user interface for QE20 inner door. Designed for up to 16 WIP controls, but supplied with 8 WIP fitted. To get full 16 WIPs on the module, add FP2022 (8 WIP Expansion Board).
Fire Detection, Control Panels and System Accessories
Extender user interface for QE20 inner door. Designed for up to 16 WIP controls, but supplied with 8 WIP fitted. To get full 16 WIPs on the module, add FP2022 (8 WIP Expansion Board).
| Models | SMX+650-1L-PS5, SMX+900-1L-PS5, SMX+900-1L-PS11, SMX+650-1L-PS11GL, SMX+12U1LPS11, SMX+28U1LPS11, SMX+40U1LPS11, SMX+40U1LPS11, LCM-320, LEM-320 |
|---|
| Product Code | FP2012 |
|---|---|
| Product Name | QE20 16 WIP Extender User Interface Module (8 WIP fitted) |
| Main Function | Extender UI for WIP controls; supplied with 8 WIP controls (expandable to 16) |
| Expansion Option | Add FP2022 (QE20 8 WIP Expansion Board) to provide 16 WIP controls |
| Mounting Location | QE20 inner door, 3U position |
| Mounting Hardware | 4 × M4 × 10 screws |
| Internal Connection | 4-way Power/Comms loom (connects to previous extender or to MUI MKI J2/J3) |
| Earth Requirement | Must be earthed to cabinet frame (earth daisy-chain between UI modules/blank panels) |
| Addressing | UBus address via rotary switches on the fitted 8-WIP PCB (and on expansion PCB if fitted) |
| Row Mapping | Bottom row = (Address − 1) × 8 + 1 Top row = (Address − 1) × 8 + 8 |
| Power Supply | 18–32V DC |
| Current (per 8 WIP PCB) | 5mA typ @ 24V (all LEDs off) 32mA typ @ 24V (all LEDs on) |
| LED Indicators (rear, per PCB) | POWER/LINK (green) SYSTEM FAULT (yellow) |
| Field Wiring | None |
| Kit Contents | 1 × Extender UI module 1 × 4-way Power/Comms loom (475mm) 4 × M4 × 10 screws 2 × LB0694 slide-in labels (zone/WIP) 2 × cable ties 1 × earth loom (450mm) 1 × LT0707 installation instructions |
| Operating Conditions | -5°C to +45°C, 10% to 93% RH (non-condensing) |