B-1 (Foam-Water nozzles) two-in-one fire suppressant deluge system, Open

B-1 (Foam-Water nozzles) two-in-one fire suppressant deluge system, Open

Description

All TYCO Nozzles PDF

Water isn’t the only fire-suppressant option. Foam-water deluge systems are best for spaces with ignitable liquids. Model B-1 foam-water sprinklers discharge foam from overhead sprinklers then discharge water — similar to standard spray sprinklers. This model has a unique venturi-style body that allows foam to form and release as effectively as possible. As the foam solution (a water-and-foam concentrate) flows through the inlet, air is drawn into the body of the unit. The foam solution mixed with air is agitated to create an air-aspirated foam. Then, the foam is released in a predetermined discharge pattern. The follow-up water spray is released in a pattern — similar to standard spray sprinklers.

Technical Specification

 

Property Specification
Brand Tyco
Model Series Tyco B-1 Nozzles
Thread size 1/2”
K-Factor 3.0
Orientation Upright and Pendent
Maximum Working Pressure 175 psi (12 bar)
Finish Options NB
Compliance UL and C-UL Listed
Reference Datasheet TFP840

Product specifications, approvals, and availability are subject to change without notice.
Always refer
to the latest Tyco Fire Protection Products datasheets for complete and current information.