ToggleNSW Car Stacker Fire Safety Guidelines 2026: New FRNSW Guidance for Automated Parking Systems
Fire and Rescue NSW (FRNSW) updated its position on Automated Vehicle Parking Systems (AVPS) on 18 August 2026. The revised guidance, Version 04, addresses important fire safety considerations for buildings incorporating automated parking systems, including mechanical car stackers.
The update is particularly relevant to fire protection engineers, sprinkler and hydrant contractors, building certifiers, developers and facility managers involved in residential and commercial building projects.
FRNSW considers automated parking systems containing three or more vertically stacked cars to be special hazards under the National Construction Code (NCC) 2022.
The position also highlights the importance of simultaneous water flow for fire sprinkler and hydrant systems, as referenced in AS 2419.1:2021, and directs designers to the AFAC Fire Safety for Carparks guideline.
The updated position does not introduce a new NCC amendment. Instead, it clarifies FRNSW’s expectations when assessing fire safety arrangements for automated vehicle parking systems.
Read the official FRNSW Automated Vehicle Parking Systems Position Statement, Version 04 (PDF).
What Changed in the August 2026 FRNSW Car Stacker Guidance?
The revised FRNSW position became effective on 18 August 2026 and supersedes the previous position updated on 29 April 2024.
The main purpose of the revision is to align the position with the latest referenced AFAC Fire Safety for Carparksguideline.
FRNSW endorses this AFAC guideline as appropriate guidance for practitioners designing and certifying buildings that incorporate automated vehicle parking systems.
The updated position also highlights specific considerations relating to special hazards, mechanical parking equipment and firefighting water supply.
| Fire safety consideration | FRNSW position and relevant reference |
|---|---|
| Current guidance | Version 04, effective 18 August 2026 |
| Previous position | Superseded position updated 29 April 2024 |
| Industry guidance | AFAC Fire Safety for Carparks |
| Special hazard threshold | Three or more vertically stacked cars |
| NCC reference | NCC 2022 clauses E1D17 and E2D21 |
| Sprinkler and hydrant supply | AS 2419.1:2021, Clause 2.2.8 |
| Mechanical parking equipment | AS 5124, including Appendix ZX5 |
These references provide an important starting point for assessing AVPS fire safety. The final design must still address the applicable building requirements and project-specific risks.
What Is an Automated Vehicle Parking System?
An Automated Vehicle Parking System (AVPS) is a mechanical system used to park, store or retrieve motor vehicles.
These systems can reduce the floor area needed for parking by moving vehicles vertically, horizontally or through a combination of mechanical movements.
Common arrangements include:
- Mechanical car stackers.
- Multilevel vehicle stacking systems.
- Automated parking platforms.
- Mechanised vehicle storage and retrieval systems.
AVPS installations may be used in apartment buildings, commercial developments, mixed-use properties and other sites where conventional parking space is limited.
However, the compact arrangement can create additional challenges for fire protection and firefighting access.
Vehicles may be positioned above or close to one another, and mechanical equipment can affect access to individual parking spaces.
For this reason, the fire safety assessment should consider the actual parking arrangement rather than treating every automated system as a conventional carpark.
1. Three or More Vertically Stacked Cars Are Considered a Special Hazard
One of the most important statements in the revised FRNSW position concerns vertically stacked vehicles.
FRNSW considers any AVPS comprising three or more vertically stacked cars to be a special hazard under NCC 2022 clauses E1D17 and E2D21.
These provisions relate to:
- E1D17 – Fire-fighting services and equipment
- E2D21 – Smoke hazard management
FRNSW expects the building certifier to identify what additional fire safety provisions, if any, are provided and assess whether the building’s fire safety measures are appropriate for the hazards and risks associated with the proposed AVPS.
Why Does Vertical Vehicle Stacking Matter?
Stacking vehicles vertically can create conditions that differ from conventional parking arrangements.
Potential considerations include:
- Fire spread between vehicles positioned above one another.
- Restricted firefighter access to individual vehicles.
- Obstructions affecting sprinkler discharge.
- Smoke and heat movement around the stacked arrangement.
- Access limitations created by mechanical platforms.
- The interaction between the parking equipment and building fire safety systems.
These are relevant design considerations, not a claim that every car stacker presents the same level of risk.
The assessment should reflect the proposed system, its configuration and the building in which it will operate.
Does the Special Hazard Classification Require Additional Equipment?
Not automatically.
The FRNSW position asks the certifier to determine what additional provisions, if any, are appropriate.
The outcome depends on the building design, existing fire safety measures and the risks associated with the proposed installation.
Designers should not assume that a standard carpark fire protection arrangement is sufficient without considering the AVPS configuration.
2. Simultaneous Sprinkler and Fire Hydrant Water Flow
Another important element of the FRNSW position concerns firefighting water supply.
The position refers to AS 2419.1:2021, Clause 2.2.8, which addresses simultaneous water flow for automatic fire sprinkler and fire hydrant systems when a car stacker is provided.
This is particularly important for fire protection engineers, hydraulic designers, sprinkler contractors and fire pump system designers.
Why Is Simultaneous Water Flow Important?
Automatic sprinkler systems and fire hydrant systems perform different functions.
Automatic fire sprinklers respond to heat and help control fire development within the protected area.
Fire hydrants provide water for firefighters to use during firefighting operations.
During a significant carpark fire, both systems may need to operate.
The water supply design must therefore consider the applicable simultaneous demand rather than assessing each system independently where the standard requires combined operation.
What Should Designers Check?
For projects incorporating car stackers, relevant design considerations may include:
- The required sprinkler system demand.
- The required fire hydrant system demand.
- Simultaneous operation requirements.
- Available water supply capacity.
- Fire pump performance, where pumps are required.
- Water storage arrangements, where applicable.
- System pressure and flow performance.
The final design must follow the applicable requirements of AS 2419.1 and other relevant standards.
The FRNSW position should not be interpreted as automatically requiring every existing car stacker installation to have a new fire pump or water tank.
Whether upgrades are necessary depends on the applicable requirements, approved design and assessment of the particular building.
3. AS 5124 and Appendix ZX5: Mechanical Parking Equipment Safety
The updated FRNSW position also refers to AS 5124 – Safety of machinery – Equipment for power driven parking of motor vehicles.
This standard addresses safety and electromagnetic compatibility requirements associated with the design, manufacture, erection and commissioning of powered vehicle parking equipment.
The FRNSW position explains that the AFAC Fire Safety for Carparks guideline identifies Appendix ZX5 of AS 5124as an appendix that should be treated as normative and considered with the same importance as the body of the standard.
This is an important distinction.
A normative provision forms part of the requirements to be applied within the relevant standard or assessment framework.
The FRNSW position therefore directs attention to Appendix ZX5 when AVPS designs are being assessed against the AFAC guidance.
What Does This Mean for Project Teams?
AVPS projects involve both mechanical equipment safety and building fire safety.
The relevant parties may include:
- AVPS manufacturers and installers.
- Mechanical and electrical contractors.
- Fire protection engineers.
- Building designers.
- Building certifiers.
- Commissioning personnel.
These teams should coordinate their work to ensure that the mechanical parking equipment and the building’s fire safety strategy are compatible.
The exact requirements of AS 5124 and Appendix ZX5 should be checked in the standard itself rather than inferred from the FRNSW position summary.
4. Applying the AFAC Fire Safety for Carparks Guideline
FRNSW endorses the AFAC Fire Safety for Carparks guideline as an appropriate reference for buildings incorporating automated vehicle parking systems.
The AFAC guidance provides a broader framework for considering fire safety risks in carparks.
For AVPS projects, the fire safety assessment should consider the actual vehicle storage arrangement, building layout and relevant fire protection measures.
Important areas for project review may include:
- The number of vehicles stored vertically.
- The overall AVPS configuration.
- Fire detection and alarm arrangements.
- Automatic sprinkler protection.
- Fire hydrant coverage.
- Firefighter access.
- Smoke management.
- Mechanical equipment interfaces.
- Emergency response considerations.
The specific measures required for a project should be determined through the applicable NCC provisions, relevant standards and the approved fire safety design.
The FRNSW position does not prescribe one universal fire protection arrangement for every automated parking system.
5. Fire Sprinkler Design Considerations for Car Stackers
Fire sprinkler protection is an important part of the fire safety assessment for many carpark projects.
In automated parking systems, the physical arrangement of vehicles and platforms may affect how sprinkler protection is designed.
For example, stacked vehicles and mechanical equipment may create obstructions or influence the distribution of water within the protected area.
Designers should assess the proposed arrangement against the applicable sprinkler standard and the building’s fire safety requirements.
Relevant considerations may include:
- Sprinkler locations and coverage.
- Potential obstructions from parking platforms.
- Vehicle storage positions.
- The number of stacked levels.
- Water supply performance.
- Coordination with hydrant demand.
- Access for inspection and maintenance.
These considerations should be assessed by appropriately qualified designers.
The FRNSW position does not itself specify a universal sprinkler head arrangement or spacing requirement for all AVPS installations.
6. Fire Hydrant Coverage and Firefighter Access
Automated parking systems may create challenges for firefighters because vehicles can be stored in locations that are difficult to access directly.
The FRNSW position recognises that systems with three or more vertically stacked cars can present special firefighting problems.
The building’s fire safety strategy should therefore consider how firefighters will access and manage an incident involving the AVPS.
Relevant considerations may include:
- Fire hydrant coverage.
- Fire brigade access routes.
- Water supply capacity.
- Access to vehicle storage areas.
- Potential restrictions created by mechanical equipment.
- The location of relevant fire protection controls.
- Coordination with the building’s emergency response arrangements.
These matters should be assessed during design and certification.
The assessment should demonstrate that the proposed fire safety provisions are appropriate for the identified risks.
7. What Should Building Certifiers and Fire Engineers Document?
The revised FRNSW position places responsibility on the certifier to consider whether the building’s fire safety measures are appropriate for the proposed AVPS.
For systems containing three or more vertically stacked vehicles, the special hazard assessment should be clearly documented.
A project file may include:
- The proposed AVPS configuration and number of vertically stacked vehicles.
- The applicable NCC provisions.
- The current FRNSW position statement.
- The relevant AFAC Fire Safety for Carparks guidance.
- The applicable AS 5124 requirements.
- The fire safety measures provided for the installation.
- Relevant sprinkler and hydrant design information.
- The certifier’s assessment of the identified hazards.
- Any approved Performance Solution, where applicable.
- Relevant commissioning and handover documentation.
The purpose of these records is to provide a clear basis for understanding the approved design and the decisions made during the certification process.
Not every project will require the same documents or additional fire safety measures.
8. Does the Updated Guidance Apply to Existing Car Stackers?
The publication of Version 04 does not automatically mean that all existing automated parking systems must be replaced or upgraded.
The FRNSW position is directed at practitioners designing and certifying buildings incorporating AVPS installations.
For existing buildings, the applicable requirements depend on the circumstances of the project and the relevant approval and compliance framework.
However, proposed modifications to an existing AVPS may justify a review of the building’s fire safety arrangements.
Examples include:
- Increasing the number of vertically stacked vehicles.
- Changing the AVPS configuration.
- Replacing or modifying parking platforms.
- Altering fire protection equipment.
- Changing access arrangements.
- Undertaking building work that affects the approved fire safety design.
Where changes could affect fire safety, building owners should seek advice from appropriately qualified professionals before proceeding.
9. Inspection, Testing and Maintenance Considerations
Although the FRNSW position focuses on design and certification, routine maintenance remains important for fire protection systems installed in buildings containing AVPS equipment.
Fire protection contractors should continue to follow the applicable inspection, testing and maintenance requirements for each installed system.
Relevant activities may include:
- Routine sprinkler system servicing.
- Fire hydrant system inspection and testing.
- Fire pump system maintenance.
- Fire detection and alarm system servicing.
- Recording defects and corrective actions.
- Maintaining access to fire protection equipment.
- Keeping service documentation up to date.
The FRNSW AVPS position does not itself introduce new AS 1851 routine servicing frequencies.
Existing maintenance obligations must be determined from the applicable legislation, standards and building requirements.
Fire Protection Logbooks for AVPS Buildings
Accurate maintenance records can help building owners and fire protection contractors monitor the condition of installed fire safety systems.
Fire Factory Australia supplies AS 1851 routine service logbooks for a range of fire protection equipment.
For buildings incorporating automated vehicle parking systems, relevant products may include:
Wet Pipe Sprinkler & Jacking Pump Systems Logbook
Supports the recording of applicable routine inspection and testing activities for wet pipe sprinkler and jacking pump systems.
Diesel and Electric Fire Pumpset Logbooks
Provide structured records for applicable fire pumpset inspection, testing, defects and corrective actions.
Fire Detection and Alarm Systems Logbook
Supports routine servicing records for relevant fire detection and alarm systems.
Explore the Fire Factory Australia Logbook Range or view our Fire Protection Service Books.
These products support routine maintenance documentation. They do not replace fire engineering reports, AVPS certification, commissioning records or project-specific compliance documentation.
Frequently Asked Questions
When was the FRNSW Automated Vehicle Parking Systems guidance updated?
FRNSW released Version 04 of its AVPS position statement on 18 August 2026, replacing the previous position updated on 29 April 2024.
When is a car stacker considered a special hazard?
FRNSW considers an automated vehicle parking system containing three or more vertically stacked cars to be a special hazard under NCC 2022 clauses E1D17 and E2D21.
Does every car stacker require additional fire protection equipment?
Not automatically. The building certifier should assess whether the existing and proposed fire safety measures are appropriate for the identified hazards and determine what additional provisions, if any, are needed.
Do sprinkler and hydrant systems need to operate simultaneously?
The FRNSW position refers to AS 2419.1:2021, Clause 2.2.8, concerning simultaneous water flow for automatic sprinkler and fire hydrant systems when a car stacker is provided.
The applicable design requirements should be checked against the standard and the project-specific fire protection strategy.
What is AS 5124?
AS 5124 addresses safety and electromagnetic compatibility requirements for powered vehicle parking equipment during design, manufacture, erection and commissioning.
Why is Appendix ZX5 important?
FRNSW notes that the AFAC guideline identifies Appendix ZX5 of AS 5124 as an appendix that should be treated as normative and considered with equal regard to the body of the standard.
Does the 2026 position change the National Construction Code?
No. The FRNSW position is guidance and does not introduce a new NCC amendment.
It explains how FRNSW considers the fire safety risks associated with automated vehicle parking systems under the existing regulatory framework.
Must existing car stackers be upgraded?
The updated position does not establish a blanket retrospective upgrade requirement for every existing AVPS.
The requirements for a particular building depend on its circumstances, applicable legislation and any proposed modifications.
Does the guidance change AS 1851 maintenance intervals?
No. The FRNSW position does not establish new AS 1851 routine servicing frequencies for buildings containing automated parking systems.
Conclusion
The 2026 FRNSW Automated Vehicle Parking Systems Position Statement provides important guidance for fire protection professionals working on buildings with mechanical car stackers and automated parking equipment.
The update reinforces three key considerations:
- Automated systems containing three or more vertically stacked vehicles are considered special hazards under NCC 2022 clauses E1D17 and E2D21.
- Fire sprinkler and hydrant water supply design must address applicable simultaneous flow requirements under AS 2419.1:2021.
- The AFAC Fire Safety for Carparks guideline and AS 5124, including Appendix ZX5, are important references for assessing automated parking systems.
For fire engineers, building certifiers, sprinkler and hydrant contractors, the priority is to ensure that the fire safety design reflects the actual vehicle storage arrangement and the risks associated with the proposed system.
Fire Factory Australia supports Australian fire protection professionals with AS 1851 routine service logbooks and fire safety products.
Explore our Fire Safety Logbooks or contact Fire Factory Australia for product enquiries and B2B pricing.
Official Source and Technical References
1. Fire and Rescue NSW – Automated Vehicle Parking Systems (AVPS), Position Statement Summary, Version 04
- Effective date: 18 August 2026
- Previous position: 29 April 2024
- Issuing authority: Fire and Rescue NSW, Fire Safety Branch
Read the official FRNSW Position Statement (PDF)
2. Australian Building Codes Board – National Construction Code 2022
Relevant provisions: E1D17 and E2D21.
View the National Construction Code
3. AS 2419.1:2021 – Fire Hydrant Installations
Relevant provision: Clause 2.2.8, referenced by FRNSW in relation to simultaneous sprinkler and hydrant water flow.
4. AS 5124 – Safety of Machinery: Equipment for Power Driven Parking of Motor Vehicles
Relevant reference: Appendix ZX5, as identified in the FRNSW position through the AFAC guideline.
5. AFAC – Fire Safety for Carparks
Industry guidance endorsed by FRNSW for the design and certification of buildings incorporating automated vehicle parking systems.
Information reviewed: 16 November 2026. This article provides general industry information and does not replace the official FRNSW position, applicable legislation, Australian Standards or professional fire engineering advice.