Description
Fire Detection, Control Panels and System Accessories
QE20 controller module for shallow (SECP) cabinets.
Same core control functions as the standard controller.
Used for new node or replacement in a QE20 system.
Fire Detection, Control Panels and System Accessories
QE20 controller module for shallow (SECP) cabinets.
Same core control functions as the standard controller.
Used for new node or replacement in a QE20 system.
| Models | SMX+650-1L-PS5, SMX+900-1L-PS5, SMX+900-1L-PS11, SMX+650-1L-PS11GL, SMX+12U1LPS11, SMX+28U1LPS11, SMX+40U1LPS11, SMX+40U1LPS11, LCM-320, LEM-320 |
|---|
| Product Code | FP2026 |
|---|---|
| Description | QE20 SECP Controller Module (Shallow cabinet version) |
| System Role | Main system controller (processing, I/O, comms) |
| Cabinet Type | Shallow QE20 SECP cabinets |
| Supply Voltage | 18–32 VDC |
| Current Consumption | 155 mA typical @ 24 VDC |
| Operating Temp | -5°C to +45°C |
| Humidity | 10% to 93% RH, non-condensing |
| Audio Inputs | 4 × balanced low-level inputs Input 1: transformer isolated, 315 mV rms nominal (2.8 V rms max), 30 V offset max Inputs 2–4: capacitor coupled differential, 315 mV rms nominal (1.4 V rms max), 5 V offset max |
| Audio Outputs | 2 outputs (currently not functional – leave open) |
| Comms / Ports | RS232 port (TXD, RXD, RTS, CTS) – Simplex 4100ESi protocol or Modbus Slave RTU RZDU port (isolated) for compatible Vigilant FIP QEComms (2-wire) for paging consoles (up to 16 FP0539) Micro-USB for programming/diagnostics (QE20Config) |
| Ethernet | 4 × 10/100Base-T RJ45 |
| QBus | 2 × RJ45 (data/audio) + 2 × 4-way (data, 24V @ 1A max) |
| WIP Port | WIP RIGHT RJ45 (audio chain) |
| GP Inputs | 4 × non-isolated, 4-state (Open/Normal/Alarm/Short) |
| GP Outputs | 4 × open-collector, 100 mA max, optional load supervision |
| Relays | 1 × Fault relay (change-over, normally energised, 2A @ 30VDC) 1 × GP relay (change-over, normally energised, 2A @ 30VDC) |
| Notes | MicroSD and USB-A sockets present but not supported (do not use) |