Table of Contents
ToggleFire Pumpset Logbook – Sprinkler & Hydrant Pumps (Diesel & Electric) & Jacking Pumps
A Complete Guide to AS 1851—2012 Fire Pumpset Routine Service Records
Fire pumpsets are an important part of many sprinkler and hydrant fire protection systems. Their role is to provide the water pressure and flow required for these systems to operate effectively when needed.
Because fire pumps can remain on standby for long periods, routine inspection, testing and preventive maintenance are important for confirming that pumps, controllers, starting devices, batteries, valves, alarms and associated equipment remain operational.
The Fire Pumpset Logbook – Sprinkler & Hydrant Pumps (Diesel & Electric) & Jacking Pumps provides structured routine service records for:
- Diesel Fire Pumpsets
- Electric Fire Pumpsets
- Jacking / Pressure-Maintenance Pumps
The logbook is developed around the relevant requirements of Section 3 of AS 1851—2012, incorporating Amendment No. 1.
It provides dedicated Monthly, Six-Monthly, Yearly and Five-Yearly Fire Pumpset Service Records, together with areas for recording test results, measured values, defects, corrective actions and completed repairs.
AS 1851 Section 3 applies to fire pumpsets including sprinkler, hydrant, hose reel, automatic pressure-maintenance and jacking pumpsets.
What Does the Fire Pumpset Logbook Cover?
The logbook combines three major fire pump categories into one structured service record:
- Diesel-driven sprinkler and hydrant fire pumps
- Electric-driven sprinkler and hydrant fire pumps
- Pressure-maintenance / jacking pumps
Separate service schedules are provided for diesel and electric fire pumpsets where their routine service requirements differ.
Dedicated records are also provided for jacking pumps.
This makes the logbook suitable for sites where sprinkler and hydrant systems use a combination of diesel pumps, electric pumps and pressure-maintenance pumps.
The actual title shown on the logbook is:
Sprinkler & Hydrant Pumps & Jacking Pumps Logbook – Diesel & Electric
Fire Pumpset Routine Service Frequencies
AS 1851—2012 Section 3 identifies routine service frequencies applicable to fire pumpsets.
| Pumpset / Service Type | Monthly | Six-Monthly | Yearly | Five-Yearly |
|---|---|---|---|---|
| Diesel Fire Pumpset | ✓ | ✓ | ✓ | ✓ |
| Electric Fire Pumpset | ✓ | ✓ | ✓ | ✓ |
| Jacking Pump | ✓ | ✓ | — | — |
For diesel and electric fire pumpsets, the logbook provides structured Monthly, Six-Monthly, Yearly and Five-Yearlyservice records.
Pressure-maintenance and jacking pumps have dedicated Monthly and Six-Monthly schedules under the applicable Section 3 requirements.
Monthly Diesel Fire Pumpset Service Records
The Fire Pumpset Logbook contains a dedicated Diesel – Monthly Service Record.
The record covers routine inspection and testing items including:
- pump room condition and access
- pressure-relief valve discharge
- warning signage
- pump, controller and driver identification
- valve positions
- pressure gauge readings
- water supply availability
- physical damage or deterioration
- engine start batteries
- monitor batteries
- float charge voltage
- electrolyte levels
- engine warming devices
- fuel tank level
- pump controller condition
- visual indicators, switches and sounders
- isolating switches
- safety guards
- water, oil and fuel condition
- automatic pump starting
- manual pump starting
- starting pressure
- run time
- hour-meter readings
- suction pressure
- discharge pressure
- pump speed
- alarms
- oil pressure
- engine temperature
- battery charger or alternator output
- circulation-relief valve operation
- exhaust system
- cooling water
The logbook also provides dedicated fields for recording actual measured values rather than relying only on Pass / Fail / N/A results.
Diesel Pump Pressure and Run Test Records
The Monthly diesel service page contains a dedicated test-data section for recording important operating values.
Pressure Gauge Readings
The logbook provides fields for:
- Water Supply Pressure
- Diesel System Pressure
- Electric System Pressure
- Other Pressure
Diesel Pump Battery Records
Dedicated fields are provided for:
- Monitor Battery Float Charge Voltage
- Engine Start Battery Float Charge Voltage
Pump Starting Device Records
Technicians can record:
- Starting Pressure
- Run Time
- Hour Meter
Diesel Pump Run Test Records
The run-test section provides fields for:
- Suction Pressure
- Discharge Pressure
- Running Speed
- Battery Charger / Alternator Output
- Oil Pressure
- Engine Temperature
These dedicated fields provide a structured history of diesel fire pump operating pressures, starting performance and run-test measurements.
Six-Monthly Diesel Fire Pumpset Service Records
The diesel Six-Monthly service section includes applicable requirements additional to the Monthly routine service.
The logbook provides for checking the hydro-pneumatic accumulator air pressure, where fitted.
The Six-Monthly diesel service record is incorporated alongside the Yearly and Five-Yearly schedules, allowing longer-term diesel fire pump servicing to be documented within the same logbook.
Yearly Diesel Fire Pumpset Service Records
The Yearly diesel routine service section is one of the most detailed parts of the Fire Pumpset Logbook.
It includes service and inspection records for:
- engine-start batteries
- battery condition
- battery replacement
- control battery testing
- battery charger voltage
- engine oil
- oil filters
- fuel filters
- air filters where required
- fuel hoses
- cooling hoses
- engine cooling system
- pressure-reducing valves
- heat exchanger strainers
- engine manufacturer service requirements
- pump and driver coupling
- pump bearings
- bearing oil
- right-angle gearbox oil
- non-return valves
- external corrosion survey
The Yearly section also incorporates a detailed annual diesel fire pump flow and performance test.
Annual Diesel Fire Pump Flow Test
The Fire Pumpset Logbook includes a dedicated record table for the annual diesel fire pump flow test.
The Yearly schedule records operation at:
- Shut-Off / Zero Flow
- 130% of Duty Flow
- Duty Flow
- Final Shut-Off Condition
The test table provides fields for recording:
- flow rate
- pressure
- suction pressure
- discharge pressure
- engine running temperature
- engine oil pressure
- air temperature at the engine intake manifold
- engine RPM
- installed tachometer reading
- calibrated tachometer reading
- RPM variation
For diesel-driven fire pumps, the Yearly routine includes operation at the applicable flow conditions and required run durations.
These records allow annual fire pump flow and performance results to be retained and compared over time.
Diesel Engine Start, Alarm and Control Tests
The Yearly diesel service schedule also includes applicable checks of the fire pump starting and control systems.
The logbook covers activities such as:
- simulated engine failure to start
- engine-start cycling
- alarm activation
- pump priming tank operation
- system pressure-relief valve operation
- engine overspeed shutdown
- pump operation at 50% duty flow
- pump operation at 100% duty flow
- remote pump start and stop
- indications at the FIP or remote start/stop panel
These records help document whether the fire pump and its associated control functions respond correctly during routine testing.
Five-Yearly Diesel Fire Pumpset Service Records
The diesel section includes a dedicated Five-Yearly Routine Service Schedule.
Applicable activities include:
- repacking pump glands
- overhaul of circulation-relief valves
- overhaul of pressure-relief valves
- engine cooling valve servicing
- pressure-regulating valve servicing
- new gland packing
- spindle lubrication
- checks of ball and butterfly valves
- replacement of compression-ignition engine air filters
- return of equipment to operational condition
These longer-term activities are incorporated into the diesel service record section.
Monthly Electric Fire Pumpset Service Records
The Fire Pumpset Logbook contains a separate Electric & Jacking Pumps – Monthly Service Record.
The electric fire pumpset schedule includes:
- pump area inspection
- pressure-relief valve discharge
- warning signage
- identification plates
- controller labelling
- valve positions
- pressure gauge readings
- water supply condition
- physical deterioration
- safety guards
- enclosure condition
- main isolating switch
- controller indicator lights
- automatic starting
- manual starting
- starting pressure
- run time
- suction pressure
- discharge pressure
- pump glands and mechanical seals
- abnormal noise or imbalance
- local and remote pump-running alarms
- controller battery
- battery enclosure
- battery float voltage
- restoration to operational condition
The logbook records applicable operational and test information for the electric fire pump during routine servicing.
Electric Fire Pump Test Records
The electric Monthly service page contains dedicated fields for:
- Water Supply Pressure
- Diesel System Pressure
- Electric System Pressure
- Other Pressure
- Suction Pressure
- Discharge Pressure
- Controller Battery Float Voltage
- Pump Starting Pressure
- Run Time
These fields allow technicians to record both inspection outcomes and actual electric fire pump operating values.
Six-Monthly Electric Fire Pumpset Service Records
The electric Six-Monthly service schedule includes applicable additional checks such as:
- operation on alternative power supply, where fitted
- hydro-pneumatic accumulator air pressure
Where an alternative power supply is installed, the electric pumpset is operated on that supply as part of the applicable routine service.
Yearly Electric Fire Pumpset Service Records
The Yearly electric fire pumpset section covers electrical, mechanical and performance checks including:
- controller battery condition
- battery discharge testing
- battery charger voltage
- heavy current-carrying contacts
- pump and driver coupling
- pump and motor bearing lubrication
- bearing oil replacement
- non-return valves
- external corrosion
- pump priming tanks
- pressure-relief valves
- remote start and stop operation
The logbook also includes a dedicated Yearly Full-Flow Performance Record for the electric fire pump.
Annual Electric Fire Pump Flow Test
The annual electric fire pump flow test records operation at multiple test conditions including:
- Shut-Off
- 130% Duty Flow
- Duty Flow
- Final Shut-Off Condition
The dedicated test table records:
- flow
- pressure
- suction pressure
- discharge pressure
- air temperature at the electric motor
- motor speed
- Phase 1 current
- Phase 2 current
- Phase 3 current
These records provide a structured history that can be used to compare electric fire pump performance across successive annual tests.
Five-Yearly Electric Fire Pumpset Service Records
The electric section also contains a Five-Yearly Routine Service Schedule.
Applicable activities include:
- pump gland repacking
- overhaul of applicable relief and regulating valves
- gland packing replacement
- spindle lubrication
- checking ball and butterfly valves for leakage
- return of equipment to operational condition
These records are incorporated within the same service section as the Six-Monthly and Yearly electric fire pump records.
Jacking Pump Monthly Service Records
The Fire Pumpset Logbook also includes dedicated routine service records for jacking pumps, also known as pressure-maintenance pumps.
The Monthly schedule covers:
- pump area condition
- pressure-relief valve discharge
- physical damage and deterioration
- safety guards
- valve positions
- water supply tank
- main isolating switch
- controller status
- indicator lamps
- manual operation
- automatic operation
- pump cut-in pressure
- pump cut-out pressure
AS 1851 includes pressure-maintenance and jacking pumps within Section 3, with dedicated routine service requirements.
Jacking Pump Cut-In and Cut-Out Pressure Records
The logbook provides separate pressure records for two jacking pumps.
Jacking Pump 1
- Cut-In Pressure
- Cut-Out Pressure
Jacking Pump 2
- Cut-In Pressure
- Cut-Out Pressure
Values are recorded in kPa, allowing technicians to maintain a clear history of the pressure settings and operation of each jacking pump.
These records can help track whether the pressure-maintenance pump is starting and stopping at the intended system pressures.
Six-Monthly Jacking Pump Service Records
The Six-Monthly jacking pump schedule includes completion of the applicable Monthly service activities and verification of the hydro-pneumatic accumulator air pressure, where applicable.
These records are incorporated into the Electric & Jacking Pumps Six-Monthly / Yearly / Five-Yearly service section.
Recording Fire Pumpset Defects and Corrective Actions
The Fire Pumpset Logbook includes dedicated areas for recording:
Item No. | Defect Type | Results / Comments | Corrective Action | Completed Repairs
The Notes section also allows servicing and rectification work to be linked to an:
Associated Logbook Sheet ID / Report Number
This provides a clear trail from routine inspection through to an identified defect, corrective action and completed repair.
Site, Technician and Service Provider Records
Each service page includes fields for:
- Site Name
- Site Address
- Site ID
- Work Order Number
- System Location
- Service Provider Details
- Date
- Report Number
- Technician Name
- Licence Number
- Client Name
- Signatures
The logbook also uses separate NCR copies for:
- Owner / Occupier / Agent
- Service Provider
- Book Copy
This supports clear distribution and retention of routine fire pumpset service records.
Why Are Fire Pump Service Records Important?
Fire pumps may remain inactive for extended periods and then be expected to operate when required.
A structured Fire Pump Service Record provides a chronological history of:
- routine inspections
- pump starts
- pressure readings
- battery checks
- controller status
- flow tests
- mechanical servicing
- electrical servicing
- identified defects
- repairs
- longer-term maintenance
AS 1851 Section 3 requires applicable routine service activities and results to be recorded in accordance with the general routine service record requirements of the Standard.
For fire pumpsets, this service history is particularly useful because performance readings can be compared across successive service visits and annual flow tests.
AS 1851—2012 Fire Pumpset Requirements in NSW
From 13 February 2026, requirements changed in NSW for the maintenance of applicable essential fire safety measures in new and existing Class 1b and Class 2 to Class 9 buildings.
Where a fire pumpset forms part of an applicable essential fire safety measure, relevant inspection and testing must be carried out in accordance with AS 1851—2012, unless the maintenance activity is addressed by an applicable Performance Solution.
Typical building classifications include:
| Building Class | Typical Examples |
|---|---|
| Class 1b | Small boarding houses, guest houses, hostels and similar accommodation |
| Class 2 | Apartment buildings |
| Class 3 | Hotels, larger boarding houses and other residential accommodation |
| Class 5 | Office buildings |
| Class 6 | Shops, restaurants and cafés |
| Class 7 | Car parks and warehouses |
| Class 8 | Factories and laboratories |
| Class 9 | Hospitals, schools and assembly buildings |
Building owners should check their Fire Safety Schedule (FSS) and other applicable building documentation to identify the essential fire safety measures applicable to their building.
NSW Government – Building Fire Safety Requirements under AS 1851—2012
Keeping Fire Pumpset Service Records in NSW
Current NSW Government guidance requires building owners to retain prescribed AS 1851 records for at least seven years and make them available for inspection.
The guidance also addresses the requirement for service activities to be documented and physical records to be maintained on site.
For fire pumpsets, these records can provide a history of:
- Monthly testing
- Six-Monthly servicing
- annual flow testing
- pressure readings
- battery servicing
- performance measurements
- Five-Yearly maintenance
- identified defects and corrective actions
NSW Government – Responsibilities of Building Owners under AS 1851—2012
Who Should Carry Out Fire Pumpset Routine Servicing?
Fire pumpsets can involve mechanical, electrical, hydraulic and control equipment.
Routine inspection, testing and servicing should therefore be carried out by persons with the appropriate competency and any licences or qualifications required for the work being undertaken.
Some fire pump activities may require specialist electrical, plumbing or mechanical expertise.
Building owners and responsible persons should ensure that the people carrying out the applicable service activities are appropriately competent for the work.
Why Use a Hardcopy Fire Pumpset Logbook?
A structured physical Fire Pumpset Logbook provides an accessible record of the pumpset’s service history.
For fire pumpsets, the service history can include:
- Monthly pump testing
- Six-Monthly servicing
- annual flow testing
- battery replacement
- pressure readings
- flow and performance readings
- Five-Yearly maintenance
- defects
- corrective actions
Keeping these records together makes it easier for technicians, building managers and future service providers to review previous servicing and identify when longer-term maintenance activities are due.
About the AS 1851 Fire Pumpset Logbook
The Fire Pumpset Logbook – Sprinkler & Hydrant Pumps (Diesel & Electric) & Jacking Pumps is a dedicated AS 1851 Section 3 Fire Pump Service Record for documenting inspection, testing, maintenance and performance information.
Designed around the applicable requirements of AS 1851—2012 Section 3, it provides structured records for:
Diesel Fire Pumps · Electric Fire Pumps · Jacking Pumps / Pressure-Maintenance Pumps
The logbook includes Monthly, Six-Monthly, Yearly and Five-Yearly service records, together with dedicated fields and tables for:
- pump starting pressure
- suction pressure
- discharge pressure
- flow rate
- battery voltage
- battery replacement
- engine temperature
- oil pressure
- engine RPM
- electric motor temperature
- electrical current
- run time
- hour-meter readings
- jacking pump cut-in pressure
- jacking pump cut-out pressure
- annual fire pump flow testing
- defects
- corrective actions
- completed repairs
For Australian fire protection contractors, fire pump technicians, building managers and facility managers, the logbook provides one organised location for maintaining applicable diesel fire pump, electric fire pump and jacking pump routine service records.
It can be used as a structured Fire Pump Logbook, Diesel Fire Pump Logbook, Electric Fire Pump Logbook, Sprinkler Pump Logbook, Hydrant Pump Logbook and Jacking Pump Service Record for applicable Section 3 activities.
Designed to support routine service and record keeping in accordance with the relevant requirements of Section 3 of AS 1851—2012.
Frequently Asked Questions
What is a Fire Pumpset Logbook?
A Fire Pumpset Logbook is used to document applicable routine inspection, testing, preventive maintenance and service results for fire pumpsets.
This logbook provides dedicated records for diesel fire pumps, electric fire pumps and jacking pumps based on the relevant requirements of AS 1851—2012 Section 3.
Which section of AS 1851 applies to fire pumpsets?
Fire pumpsets are covered under Section 3 of AS 1851—2012.
This includes applicable sprinkler, hydrant, hose reel, pressure-maintenance and jacking pumpsets.
What pumps are included in this logbook?
The logbook includes dedicated records for:
- diesel sprinkler and hydrant pumps
- electric sprinkler and hydrant pumps
- jacking / pressure-maintenance pumps
How often are fire pumpsets serviced under AS 1851—2012?
The applicable frequencies depend on the pumpset type and service activity.
The logbook provides Monthly, Six-Monthly, Yearly and Five-Yearly records for diesel and electric fire pumpsets and dedicated Monthly and Six-Monthly records for jacking pumps.
Does the logbook include diesel fire pump service records?
Yes.
It includes dedicated Monthly, Six-Monthly, Yearly and Five-Yearly diesel fire pumpset service records.
Does it include electric fire pump service records?
Yes.
Separate Monthly, Six-Monthly, Yearly and Five-Yearly records are provided for electric fire pumpsets.
Does the logbook include jacking pumps?
Yes.
Dedicated Monthly and Six-Monthly service schedules are included for jacking pumps.
Can jacking pump cut-in and cut-out pressures be recorded?
Yes.
Dedicated fields are provided for the cut-in and cut-out pressures of Jacking Pump 1 and Jacking Pump 2.
Does the logbook include annual fire pump flow testing?
Yes.
Detailed Yearly flow-test records are provided for both diesel and electric fire pumps.
What diesel fire pump values can be recorded?
The diesel fire pump records include:
Flow | Suction Pressure | Discharge Pressure | Engine Temperature | Oil Pressure | Intake-Air Temperature | RPM
Battery and starting-device information can also be recorded.
What electric fire pump values can be recorded?
The electric fire pump records include:
Flow | Suction Pressure | Discharge Pressure | Motor Temperature | Motor Speed | Phase 1 Current | Phase 2 Current | Phase 3 Current
Are battery records included?
Yes.
The logbook includes applicable fields for battery float voltage, battery replacement, battery discharge testing and battery charger voltage.
Can defects and corrective actions be recorded?
Yes.
Dedicated fields are provided for:
Defect Type | Results / Comments | Corrective Action | Completed Repairs
Is AS 1851—2012 mandatory in NSW?
For applicable essential fire safety measures, NSW requirements changed from 13 February 2026.
Where a fire pumpset forms part of an applicable essential fire safety measure, the relevant maintenance activities must be carried out in accordance with AS 1851—2012 unless an applicable Performance Solution addresses the maintenance activity.
How long must applicable AS 1851 records be retained in NSW?
Current NSW Government guidance requires prescribed AS 1851 records to be retained for at least seven years and made available for inspection.
Does using this logbook automatically make a fire pump system compliant with AS 1851?
No.
The logbook provides a structured method for recording applicable routine service activities.
Compliance also depends on the actual system, approved design, servicing performed, completed tests, competent personnel, identified defects and applicable regulatory requirements.
Conclusion
The Fire Pumpset Logbook – Sprinkler & Hydrant Pumps (Diesel & Electric) & Jacking Pumps provides a comprehensive and organised way to document routine servicing of fire pumps used with sprinkler and hydrant systems.
By combining diesel fire pump, electric fire pump and jacking pump service records in one document, it supports applicable Monthly, Six-Monthly, Yearly and Five-Yearly servicing together with detailed flow, pressure, battery, engine, motor and performance records.
For fire protection contractors, technicians and building managers, it provides a practical AS 1851 Section 3 Fire Pumpset Service Record for maintaining a clear and traceable history of fire pump inspection, testing and maintenance.
Designed to support routine service and record keeping in accordance with the relevant requirements of AS 1851—2012 Section 3.
Explore Our Complete Fire Safety Logbook Range
Looking for logbooks for other fire protection systems?
Fire Factory Australia provides a comprehensive range of AS 1851—2012 Fire Safety Logbooks for routine inspection, testing, servicing and maintenance records across a wide range of fire protection systems.
Our range includes logbooks for fire detection and alarm systems, emergency warning systems, sprinkler systems, fire pumps, hydrants, hose reels, water storage tanks, special hazard systems, passive fire protection, mechanical fire and smoke control systems, emergency and exit lighting, and other fire protection equipment.
View Our Complete Range of Fire Safety Logbooks

