Fire Detection & Alarm Systems and Emergency Warning & Intercom Systems Logbook
Combined AS 1851—2012 Section 6 Routine Service Records
Fire Detection & Alarm Systems and Emergency Warning & Intercom Systems perform closely related functions within a building’s fire safety and emergency communication arrangements.
Fire detection equipment identifies alarm conditions and initiates relevant system responses. Emergency warning equipment communicates warning signals to building occupants, while emergency intercom equipment enables communication between the emergency control point and Warden Intercom Points (WIPs).
Where these systems are installed together, maintaining their service records in separate books can create additional administration for technicians and building managers.
The Fire Detection & Alarm Systems and Emergency Warning & Intercom Systems Logbook from Fire Factory Australia brings their applicable routine service records together in one dedicated hardcopy book.
Developed around AS 1851—2012 (Incorporating Amendment No. 1), Section 6, the logbook provides structured records for:
- Fire Detection & Alarm Systems
- Smoke & Heat Alarms
- Emergency Warning Systems
- Emergency Intercom Systems
- Fire Detection & Control Equipment Associated with Special Hazard Systems
- Smoke Hazard Management Detection & Control Functions
- Fire Detectors & Sampling Points
- System Batteries
- Occupant Warning Functions
- System Interfaces
- Warden Intercom Points
- Speaker Circuits
The combined logbook includes Monthly, Six-Monthly, Yearly and Five-Yearly service record sections, depending on the equipment and applicable schedule.
One Logbook. Two Essential Systems.
Explore the Combined Fire Detection & Emergency Warning Logbook
Why Choose a Combined Fire Detection & Emergency Warning Logbook?
Fire Detection & Alarm Systems and Emergency Warning & Intercom Systems are often connected through the building’s fire safety infrastructure.
A fire alarm may originate at a Fire Indicator Panel (FIP), activate occupant warning functions, communicate with an Emergency Warning System and initiate other connected building systems.
When both system groups are installed at the same site, a combined service record offers a practical way to document their related inspection and testing activities.
The combined logbook provides:
- One physical book for both system groups
- Dedicated schedules for each applicable system
- Fire detector and sampling-point test records
- Battery capacity and condition fields
- Emergency warning acoustic measurements
- Warden Intercom Point communication records
- System interface test records
- Defect and corrective-action documentation
The combined format does not remove the distinction between the systems or their service requirements.
Each system retains its relevant AS 1851 schedule references and dedicated recording areas.
For sites requiring only one system group, Fire Factory Australia also offers separate Fire Detection & Alarm Systemsand Emergency Warning & Intercom Systems logbooks.
What Systems Does the Combined Logbook Cover?
The logbook brings together several related systems and functions addressed under AS 1851—2012 Section 6.
| System or Equipment | Records Included |
|---|---|
| Fire Detection & Alarm Systems | Monthly, Yearly and Five-Yearly |
| Smoke & Heat Alarms | Six-Monthly and Yearly |
| Special Hazard Detection & Control Equipment | Six-Monthly and Yearly |
| Smoke Hazard Management Detection & Control Functions | Yearly |
| Emergency Warning Systems | Monthly, Yearly and Five-Yearly |
| Emergency Intercom Systems | Yearly |
| Fire Detectors & Sampling Points | Dedicated test records |
| System Batteries | Capacity and condition records |
| System Interfaces | Applicable functional testing |
| Speaker Circuits | Five-Yearly impedance records |
The Special Hazard and Smoke Hazard Management entries relate to their applicable Section 6 detection, control and indication functions.
They do not replace the complete service records required for suppression equipment or mechanical smoke-control installations.
AS 1851 Routine Service Frequency Summary
Different systems require different routine service schedules.
The combined logbook includes the following sections:
| System | Monthly | Six-Monthly | Yearly | Five-Yearly |
|---|---|---|---|---|
| Fire Detection & Alarm Systems | ✓ | — | ✓ | ✓ |
| Smoke & Heat Alarms | — | ✓ | ✓ | — |
| Special Hazard Detection & Control Equipment | — | ✓ | ✓ | — |
| Smoke Hazard Management Detection & Control Functions | — | — | ✓ | — |
| Emergency Warning Systems | ✓ | — | ✓ | ✓ |
| Emergency Intercom Systems | — | — | ✓ | — |
These are the dedicated schedules included in the product.
The appropriate activities must be determined from the installed equipment and applicable AS 1851 requirements.
Monthly Fire Detection & Alarm System Service Records
The Monthly Fire Detection & Alarm System schedule is based on Table 6.4.1.2 of AS 1851—2012.
It includes inspection and testing activities relating to:
- External alarm bells and strobes
- Fire Indicator Panels
- Sub-Indicator Panels
- Repeater panels
- Fire Brigade Panels
- Mimic panels
- Fire Fan Control Panels
- Panel visibility and accessibility
- Dust and contamination
- Panel-door identification
- Manual Call Point replacement elements and tools
- Battery enclosure corrosion
- Simulated alarm conditions
- Visual and audible alarm indications
- Alarm Signalling Equipment
- Occupant warning system operation
- Visual Warning Devices
- Isolate and disable indications
- Monitoring-service indications, where applicable
- Visual indicators
- Zone block plans
- Supplementary drawings
These records document the system’s basic condition and operational response during monthly servicing.
Fire Indicator Panel & Control Equipment Inspection
The Fire Indicator Panel is a central component of many Fire Detection & Alarm Systems.
The Monthly Schedule provides records for inspection of applicable:
- Fire Indicator Panels (FIP)
- Sub-Indicator Panels (SIP)
- Repeater panels
- Fire Brigade Panels (FBP)
- Mimic panels
- Fire Fan Control Panels (FFCP)
Relevant checks include visibility, accessibility, identification and the presence of dust or contaminants.
The logbook provides a dedicated record of these inspections as part of the wider fire detection service history.
Fire Alarm Simulation & Occupant Warning Testing
The Monthly Fire Detection & Alarm System schedule includes simulation of an alarm condition.
Applicable checks confirm that:
- Required visual indications operate
- Required audible indications operate
- External alarms activate
- Alarm Signalling Equipment operates where applicable
- Occupant warning functions activate
- Visual Warning Devices respond as required
These tests are particularly relevant where the fire detection system initiates warning functions or communicates with other building fire safety equipment.
The combined logbook provides a single location for retaining the associated records.
Monthly Emergency Warning System Service Records
Emergency Warning Systems have a separate Monthly Service Schedule within the combined book.
This schedule includes records for:
- Zone block plans
- Supplementary zone drawings
- Emergency Warning System panel
- Panel visibility
- Accessibility
- Cleanliness
- Panel labelling
- Spare frangible elements and replacement tools, where required
- Vented battery enclosure corrosion
- Simulated alarm conditions
- Operation of required warning signals
The Monthly Emergency Warning System record remains distinct from the Monthly Fire Detection & Alarm System record.
This helps ensure the applicable activities for each system are documented.
Six-Monthly Smoke & Heat Alarm Service Records
The combined logbook includes a dedicated Six-Monthly Smoke & Heat Alarm schedule.
It provides records for inspection of applicable alarms for:
- Physical damage
- Dust and contamination
- Battery indication
- Mains-power conditions that may affect operation
The schedule also includes operation of the alarm test function to verify the required audible indication.
Other sensory warning devices are inspected where fitted.
The dedicated record allows smoke and heat alarm servicing to be documented separately from the main Fire Detection & Alarm System checklist.
Six-Monthly Special Hazard Detection & Control Records
The combined logbook includes applicable Section 6 records for Fire Detection & Control Equipment Associated with Special Hazard Systems.
The Six-Monthly schedule includes activities relating to:
- Local Control Stations (LCS)
- Visual Warning Devices
- Discharge inhibit controls
- Automatic/manual controls
- Manual initiation switches
- System-inoperative indications
- Discharge actuator circuit faults
- Lock-off valve indications, where fitted
- Manual inhibit switches, where fitted
- Supervised actuator circuits
- Actuator functions
- System logic
These records concern the applicable electrical detection and control equipment.
They do not replace servicing of the complete suppression installation, including extinguishing agent, cylinders, pipework, nozzles and other suppression components.
For those records, see the Special Hazard Fire Suppression Systems Logbook.
Yearly Fire Detection & Alarm System Service Records
The Yearly Fire Detection & Alarm System schedule includes more detailed inspection, testing and survey activities.
The combined logbook provides records relating to:
- Manual Call Points
- Warning devices
- Panel switches and keypads
- Visual indicators
- Alphanumeric displays
- System batteries
- Fire detectors
- Occupant warning systems
- Sound Pressure Levels
- Alarm acknowledgement facilities
- Alarm investigation facilities
- Battery condition
- Detector and equipment service life
- System changes or damage
- Detector suitability
- Nuisance alarm conditions
- Exposed cabling and conduits
- Control and Indicating Equipment
- System interfaces
Dedicated measurement tables support several of these activities.
Fire Detector & Sampling Point Test Records
The combined logbook includes dedicated Fire Detector & Sampling Point Test Records associated with Appendix G of AS 1851—2012.
These records provide fields for:
| Record Field | Information |
|---|---|
| Date | Test date |
| Loop No. | Detector loop identification |
| Alarm Zone | Alarm zone identification |
| Detector / Sampling Point | Equipment identification and result |
| Detector Type | Detector classification |
| Lower Response Limit | Applicable lower limit |
| Upper Response Limit | Applicable upper limit |
| Reference | Reference information |
Individual detector and sampling-point results can be recorded separately from the main Yearly checklist.
This provides a more detailed history of detector testing.
Fire Detection System Battery Capacity Records
The Yearly Fire Detection & Alarm System section includes dedicated battery capacity fields.
| Measurement | Unit |
|---|---|
| Quiescent Current (IQ) | A |
| Maximum Alarm Current (IA) | A |
| Calculated Capacity | Ah |
| Installed Capacity | Ah |
The applicable schedule includes measuring the system currents and checking that the installed battery capacity meets the calculated requirement.
These records provide a reference for future servicing and battery assessment.
Fire Detection System Battery Condition Records
The combined logbook also includes battery condition fields for:
- Date Last Replaced
- Test Load Current
- Final Test Voltage
The source schedule includes battery-condition verification by discharge testing for applicable batteries more than two years old.
The dedicated fields allow replacement dates and test measurements to be retained with the Fire Detection & Alarm System records.
Occupant Warning System Sound Pressure Level Records
The Yearly Fire Detection & Alarm System section includes a dedicated table for Occupant Warning System Sound Pressure Level (SPL) measurements.
| Record Field | Unit |
|---|---|
| Location of Reference Point | Location |
| Required SPL | dBA |
| Measured SPL | dBA |
These records allow the measured sound pressure level to be compared with the applicable reference requirement.
They relate to the occupant warning functions addressed in the Fire Detection & Alarm System schedule.
The combined book also includes separate Emergency Warning System acoustic records under its Five-Yearly schedule.
Fire Detection System Interface Testing
Fire Detection & Alarm Systems may communicate with multiple building systems.
The combined logbook includes an interface recording area covering applicable functions such as:
- Fire Door Release
- Security Door Release
- Roof Vents
- Warning System / Intercom
- Plant Shutdown
- Fuel Shut-off
- Elevator Override
- Exit Pressurisation
- Smoke Control
- Smoke Exhaust
- Air Handling / HVAC
- Control and Indicating Equipment fault indication
- Special Hazard Systems
- Notification / Alert Systems
- Other applicable interfaces
The Yearly Schedule includes simulation of alarm conditions and verification that the relevant interface transmission paths initiate the corresponding systems as required.
This is an important part of documenting the relationship between detection, warning and connected building equipment.
Yearly Smoke Hazard Management Detection & Control Records
The combined logbook includes Yearly records for applicable Smoke Hazard Management detection and control functions.
These records address:
- Fire Fan Control Panel fire-mode operation
- Manual ON–AUTO–OFF override controls
- Airflow fault indication
- Air-handling equipment interconnecting cable faults
- Electricity phase-fail indication
- Fan-running indication
- Fan-stopped indication
- Fan-fault indication
These activities relate to the applicable Section 6 control and indication functions.
They should not be confused with routine servicing of the mechanical equipment itself.
For fans, dampers, smoke-control equipment and other mechanical fire/smoke control features, use the Mechanical Services Logbook – Fire/Smoke Control Features.
Yearly Special Hazard Detection & Control Records
The combined logbook also includes applicable Yearly activities for Special Hazard detection and control equipment.
These include:
- Suppression-system status monitoring
- Indication of monitored functions at the suppression-system control panel
- Simulation of system operation
- Electrical directional valve operation
- System discharge sequence
- Time-delay recording
- Agent-release detection
- Agent-release indication at the FIP
These records document the relevant detection, monitoring and control functions.
They do not replace the complete routine service records required for the suppression system.
Yearly Emergency Warning System Service Records
The Yearly Emergency Warning System schedule provides a detailed inspection and functional testing record.
It includes activities relating to:
- Emergency Call Points
- Visual Warning Devices
- Other warning devices
- As-installed drawings
- Automatic warning operation
- Speaker-circuit faults
- Emergency call-point circuit faults
- Visual Warning Device circuit faults
- Emergency Warning Panel indications
- FIP and SIP indications
- Aural indicators
- Panel switches
- Keypad controls
- Visual indicators
- Alphanumeric displays
- Battery capacity
- Ancillary control functions
- Warning-system audibility
- Non-emergency signal override
- Interfaced systems
- Battery condition
- Building changes
- Occupancy changes
This dedicated schedule provides the Emergency Warning System with its own service history within the combined book.
Emergency Warning System Battery Records
The Emergency Warning System section includes fields for:
| Record Field | Unit |
|---|---|
| Quiescent Current (IQ) | A |
| Alarm Current (IA) | A |
| Battery Capacity | Ah |
| Date Last Replaced | Date |
| Test Load Current | A |
| Final Test Voltage | V |
These fields support documentation of applicable battery capacity and condition activities.
The measurements are retained alongside the Yearly Emergency Warning System inspection and testing results.
Emergency Warning System Audibility & Interface Testing
The Yearly Emergency Warning System schedule includes testing of warning signal audibility.
It also includes checking that emergency warning signals override non-emergency audible signals.
Where the system interfaces with other fire protection or building equipment, applicable functional interface testing is recorded.
These activities help document the warning system’s operation within the wider building fire safety installation.
Yearly Emergency Intercom System Service Records
The combined logbook includes a dedicated Yearly Emergency Intercom System schedule.
It provides records for:
- Emergency Intercom Panel
- Visual indicators
- Alphanumeric displays
- Aural indicators
- Panel switches
- Keypad controls
- WIP circuit faults
- Reset function
- Warden indicators and controls
- Warden Intercom Points
- WIP visibility and accessibility
- WIP mechanical condition
- Battery enclosure
- Outgoing WIP calls
- Incoming WIP calls
- All-call function
- Stand-alone intercom battery capacity
- System interfaces
- Battery condition
- Structural changes
- Occupancy changes
- Evacuation-zone WIP provision
These records remain separate from the Emergency Warning System schedule, despite being included in the same physical book.
Warden Intercom Point (WIP) Inspection & Testing
Warden Intercom Points provide communication between the emergency control point and wardens.
The Yearly Emergency Intercom Schedule includes inspection of WIPs for:
- Visibility
- Accessibility
- Identification
- Mechanical damage
It also includes functional communication testing.
Outgoing WIP Calls
A call is initiated from each WIP.
The test verifies correct indication and clear communication with the intercom panel operator.
Incoming WIP Calls
A call is initiated from the intercom panel to each WIP.
The test verifies correct indication and clear communication.
All-Call Function
The all-call address function is tested to confirm that the applicable visual indication activates and the address can be heard at the WIP phones.
Together, these records document the main communication functions of the Emergency Intercom System.
Emergency Intercom Battery Capacity Records
For applicable stand-alone Emergency Intercom Systems, the combined logbook provides fields for:
- Quiescent Current
- Alarm Current
- Battery Capacity
- Nominal Capacity
- Battery replacement information
- Battery condition information
The source schedule also includes discharge testing for applicable batteries more than two years old.
These records allow the intercom battery history to be maintained separately from the Fire Detection and Emergency Warning battery records.
Five-Yearly Fire Detection & Alarm System Service Records
The Five-Yearly Fire Detection & Alarm System schedule provides additional functional verification.
The combined logbook includes records for:
- Supervised input circuits
- Supervised output circuits
- FIP circuit faults
- Required visual fault indications
- Required audible fault indications
- Alarm Signalling Equipment, where applicable
- Short-circuit isolation
- Power-supply supervision
- Collective fire-detection circuits
- System interfaces
- Loudspeaker circuit impedance
- Monitoring-link faults
- Alarm verification facilities
These activities are documented in the dedicated Five-Yearly Fire Detection & Alarm System section.
Five-Yearly Emergency Warning System Service Records
The Emergency Warning System has a separate Five-Yearly schedule.
It includes three important measurement areas:
- Speech Intelligibility
- Sound Pressure Level
- Speaker-Circuit Impedance
These records provide additional acoustic and electrical measurements beyond the routine Monthly and Yearly Emergency Warning System activities.
Speech Intelligibility Test Records
The Five-Yearly Emergency Warning System section provides fields for:
| Record Field | Information |
|---|---|
| Location | Test location |
| Reference CIS | Reference value |
| Recorded CIS | Measured result |
Testing is undertaken in applicable areas where speech intelligibility is required.
The records allow measured results to be compared with the relevant reference values.
Emergency Warning Sound Pressure Level Records
The Five-Yearly Emergency Warning System section also provides fields for:
| Record Field | Unit |
|---|---|
| Location | Reference point |
| Reference SPL | dBA |
| Measured SPL | dBA |
These measurements provide a record of the sound pressure level at the applicable reference locations.
Emergency Warning Speaker-Circuit Impedance Records
The Five-Yearly Emergency Warning System section includes a speaker-circuit impedance table.
The fields are:
Circuit | Required Impedance | Measured Impedance
The source schedule identifies checks relating to changes in impedance from the previous test and the applicable rated amplifier output.
The measurements can be retained in the combined logbook alongside the speech intelligibility and SPL results.
Defects, Test Results & Corrective Actions
The combined logbook provides dedicated areas for recording:
Item No. | Defect Type | Results / Comments | Corrective Action | Completed Repairs
These fields allow technicians to document:
- The equipment or service item
- The defect identified
- Inspection observations
- Test results
- Required corrective action
- Completed repairs
The records can therefore show more than a simple pass or fail result.
They provide a traceable history of the service activity and any associated rectification work.
One Combined Logbook or Two Separate Logbooks?
Fire Factory Australia offers both formats.
| Product | Intended Record Coverage |
|---|---|
| Combined Fire Detection & Emergency Warning Logbook | Both Fire Detection/Alarm and Emergency Warning/Intercom system groups |
| Fire Detection & Alarm Systems Logbook | Fire Detection/Alarm and associated Section 6 records |
| Emergency Warning & Intercom Systems Logbook | Emergency Warning and Emergency Intercom records |
The combined version is designed for sites where both system groups are installed and one consolidated service record is preferred.
For sites requiring separate books, the dedicated products are available:
Fire Detection & Alarm Systems Logbook
Emergency Warning & Intercom Systems Logbook
The appropriate format depends on the equipment installed and the site’s record-keeping arrangements.
AS 1851—2012 Section 6
AS 1851—2012 is the Australian Standard for the routine servicing of fire protection systems and equipment.
Section 6 addresses fire detection and alarm systems and includes the relevant service requirements for associated warning, intercom, detection and control functions.
The combined logbook brings together multiple Section 6 schedules in one physical book while retaining the relevant service frequency and recording requirements for each system.
It is designed to support documentation of:
- Inspection
- Functional testing
- Preventive maintenance
- Survey activities
- Measurements
- Defects
- Corrective actions
The logbook is a record-keeping tool and does not replace the Standard or the need to carry out the required service activities.
AS 1851—2012 Requirements in NSW
From 13 February 2026, NSW requires applicable essential fire safety measures in new and existing Class 1b and Class 2–9 buildings to be maintained in accordance with AS 1851—2012, subject to applicable alternative maintenance arrangements specified by a Performance Solution.
This does not mean every building within these classifications contains all the systems covered by the combined logbook.
The relevant measures depend on the building and its applicable fire safety documentation.
Building owners should refer to the building’s Fire Safety Schedule and other relevant documents to identify the systems requiring maintenance.
NSW Government – Building fire safety requirements under AS 1851—2012
Who Is the Combined Logbook Designed For?
The combined logbook is intended for professional use by:
- Fire protection contractors
- Fire detection technicians
- Emergency warning technicians
- Emergency intercom technicians
- Building managers
- Facility managers
- Property maintenance teams
- Service providers responsible for multiple Section 6 systems
Applicable servicing should be carried out by suitably competent personnel and appropriately licensed persons where required.
About the Combined Fire Detection & Emergency Warning Logbook
The Fire Detection & Alarm Systems and Emergency Warning & Intercom Systems Logbook provides one organised location for maintaining related Section 6 service records.
Its key record areas include:
| Section | Main Records |
|---|---|
| Monthly Fire Detection & Alarm | Panel inspection, alarm simulation and warning functions |
| Monthly Emergency Warning | Panel inspection and warning signal testing |
| Six-Monthly Smoke & Heat Alarm | Condition and alarm testing |
| Six-Monthly Special Hazard Detection/Control | Control equipment, release functions and indications |
| Yearly Fire Detection & Alarm | Detector testing, batteries, interfaces and surveys |
| Yearly Smoke Hazard Management | Detection and control functions |
| Yearly Special Hazard Detection/Control | Monitoring, release sequence and indications |
| Yearly Emergency Warning | Warning devices, faults, batteries, audibility and interfaces |
| Yearly Emergency Intercom | WIP testing, communication functions and batteries |
| Five-Yearly Fire Detection & Alarm | Circuit supervision, fault testing and interfaces |
| Five-Yearly Emergency Warning | Speech intelligibility, SPL and speaker impedance |
The logbook also provides dedicated areas for measurements, defects and corrective actions.
One Logbook. Two Essential Systems.
Frequently Asked Questions
What is a combined Fire Detection & Emergency Warning Logbook?
It is a dedicated record book that brings together applicable Fire Detection & Alarm System and Emergency Warning & Intercom System routine service records.
The product is developed around AS 1851—2012 Section 6.
Why use a combined logbook instead of two separate books?
The combined format allows related service records to be maintained within one physical book where both system groups are installed.
Each system retains its relevant service schedule and recording areas.
Which systems are included?
The logbook includes Fire Detection & Alarm Systems, Smoke & Heat Alarms, Emergency Warning Systems, Emergency Intercom Systems and applicable Section 6 detection/control functions associated with Special Hazard and Smoke Hazard Management Systems.
What service frequencies are included?
Depending on the system, the combined logbook includes Monthly, Six-Monthly, Yearly and Five-Yearly records.
Does it include Fire Indicator Panel servicing?
Yes.
The Monthly Fire Detection & Alarm System section includes inspection of applicable Fire Indicator Panels and associated control equipment.
Does it include fire detector test records?
Yes.
Dedicated Fire Detector & Sampling Point Test Records are provided for applicable detector testing associated with Appendix G.
Does it include smoke and heat alarm servicing?
Yes.
The combined logbook includes Six-Monthly and Yearly Smoke & Heat Alarm records.
Does it include Special Hazard System records?
It includes applicable detection and control equipment records under Section 6.
It does not replace the service records for the complete suppression system.
Does it include Smoke Hazard Management records?
Yes, for applicable Section 6 detection, control and indication functions.
Mechanical smoke-control equipment requires separate applicable service records.
Does it include Emergency Warning System servicing?
Yes.
The logbook includes Monthly, Yearly and Five-Yearly Emergency Warning System records.
Does it include Emergency Intercom System servicing?
Yes.
A dedicated Yearly Emergency Intercom System record is included.
Does it include Warden Intercom Point testing?
Yes.
The Emergency Intercom section includes WIP inspection, incoming calls, outgoing calls and all-call testing.
Does it include battery records?
Yes.
The logbook includes applicable battery capacity and condition records for Fire Detection, Emergency Warning and stand-alone Emergency Intercom Systems.
Does it include Speech Intelligibility testing?
Yes.
The Five-Yearly Emergency Warning System section includes Reference CIS and Recorded CIS fields.
Does it include Sound Pressure Level records?
Yes.
The combined logbook includes applicable Occupant Warning System and Emergency Warning System SPL records.
Does it include speaker-circuit impedance records?
Yes.
Applicable Five-Yearly records provide fields for required and measured speaker-circuit impedance.
Does it include system interface testing?
Yes.
The relevant schedules include applicable interface testing and recording.
Can defects and corrective actions be recorded?
Yes.
Dedicated fields are provided for defects, results, comments, corrective actions and completed repairs.
Can I purchase the Fire Detection or Emergency Warning logbooks separately?
Yes.
Fire Factory Australia also offers dedicated Fire Detection & Alarm Systems and Emergency Warning & Intercom Systems logbooks.
Does using the combined logbook guarantee compliance with AS 1851—2012?
No.
The logbook provides a structured format for documenting applicable service activities.
Compliance depends on the installed systems, approved design, work performed, test results, personnel competency, defects, corrective actions and relevant regulatory requirements.
Conclusion
The Fire Detection & Alarm Systems and Emergency Warning & Intercom Systems Logbook brings related AS 1851—2012 Section 6 routine service records together in one dedicated book.
It includes applicable Monthly, Six-Monthly, Yearly and Five-Yearly schedules for fire detection, smoke and heat alarms, emergency warning, emergency intercom and associated detection/control functions.
With dedicated records for fire detectors, batteries, occupant warning measurements, system interfaces, Warden Intercom Points, speech intelligibility, sound pressure levels, speaker-circuit impedance and corrective actions, the combined format provides an organised history of servicing across both system groups.
One Logbook. Two Essential Systems.
Designed to support routine service and record keeping in accordance with the relevant requirements of AS 1851—2012 Section 6.
Explore Our Complete Fire Safety Logbook Range
Looking for records for other fire protection systems?
Fire Factory Australia provides a range of AS 1851—2012 logbooks for sprinkler systems, fire pumps, hydrants, mechanical services, passive fire protection and other fire safety equipment.
View Our Complete Range of Fire Safety Logbooks
Table of Contents
Toggle